Voltage drop calculator (BS 7671)

Pick the cable, enter the current and the length of run — see the volt drop and whether it is inside the 3% or 5% limit.

Work out the voltage drop

VD = mV/A/m × Ib × L ÷ 1000. Limits for an installation fed from a public low-voltage supply (BS 7671 Appendix 4, Table 4Ab).

Check against BS 7671 and the manufacturer's data; this is a guide, not a design tool.

Voltage drop table for twin & earth

mV/A/m values from BS 7671 Table 4D5 (70 °C thermoplastic flat cable, conductors at operating temperature).

Twin & earth (Table 4D5) — mV/A/m and maximum run length
CablemV/A/mLtg 6 A16 A20 A32 A
1.0 mm²4426 m16 m13 m8 m
1.5 mm²2940 m25 m20 m12 m
2.5 mm²1864 m40 m32 m20 m
4 mm²11105 m65 m52 m33 m
6 mm²7.3158 m98 m79 m49 m
10 mm²4.4261 m163 m131 m82 m
16 mm²2.8411 m257 m205 m128 m

Lighting column: 3% (6.9 V) at 6 A. Other columns: 5% (11.5 V) at the current shown, single-phase 230 V. Lengths are for voltage drop only — check current-carrying capacity and Zs too.

How voltage drop is checked

BS 7671 Regulation 525 requires the voltage at the equipment to be high enough for it to work safely. Appendix 4 gives deemed-to-comply limits measured from the origin of the installation:

The formula

Voltage drop (V) = mV/A/m × Ib × L ÷ 1000, where mV/A/m is the tabulated value for the cable, Ib is the design current in amps and L is the length of run in metres. Example: 2.5 mm² twin & earth (18 mV/A/m), 20 A, 30 m → 18 × 20 × 30 ÷ 1000 = 10.8 V, which is 4.7% — inside the 5% limit for a socket circuit.

Remember the whole route

The limit covers the drop from the origin to the point of use. If the circuit is fed from a sub-main, add the sub-main's voltage drop to the final circuit's. For a ring final circuit, the usual approximation is to use a quarter of the end-to-end ring length with the full load, or follow the method in the On-Site Guide.

Three-phase circuits

For a balanced three-phase circuit use the three-phase mV/A/m column for the cable (for example in Table 4D2B or 4E2B) and compare with the 400 V limits. Twin & earth is single-phase only, so the three-phase option asks you to enter the value.

Questions electricians ask

What is the maximum voltage drop allowed in BS 7671?

For an installation supplied from a public low-voltage network, Appendix 4 of BS 7671 gives 3% for lighting circuits and 5% for other uses, measured from the origin. At 230 V that is 6.9 V and 11.5 V. Private supplies are allowed 6% and 8%.

How do you calculate voltage drop?

Multiply the cable's tabulated mV/A/m by the design current and the length in metres, then divide by 1000. For example 2.5 mm² twin and earth at 18 mV/A/m carrying 20 A over 30 m drops 10.8 V.

What is the mV/A/m of 2.5 mm² twin and earth?

BS 7671 Table 4D5 gives 18 mV/A/m for 2.5 mm² flat twin and earth, 29 mV/A/m for 1.5 mm², 11 for 4 mm², 7.3 for 6 mm² and 4.4 for 10 mm².

Does voltage drop include the sub-main?

Yes. The 3% and 5% limits apply from the origin of the installation to the equipment, so the drop in a sub-main or distribution circuit must be added to the final circuit.

More free tools for electricians

Max Zs table — MCB, RCBO and fuse limits + 80% check› Cable size calculator — Twin & earth, Table 4D5, Ca · Cg · Ci›

Test sheets on the phone

EIC, EICR and Minor Works with live Zs, insulation and RCD checks, printed on the official IET forms.

See Graftum for electricians
© 2026 Graftum Ltd · Software for electricians · Privacy
Check against BS 7671 and the manufacturer's data; this is a guide, not a design tool.