BTU calculator — radiator size for a room

Enter the room, its walls and windows — get the heat it needs in watts and BTU/h, and the radiator to fit for your system temperature.

Work out the heat a room needs

Fabric loss (U-value × area × temperature difference) plus air change loss (0.33 × air changes × volume × temperature difference). A quick estimate — not a full BS EN 12831 heat loss calculation.

−3 °C is a common UK design temperature; colder areas use lower figures. Room temperature and air changes fill in from the room type and can be changed.

This room — radiator rating to look for (ΔT50 catalogue figure)
SystemFactorWattsBTU/h

An estimate for sizing radiators, not a full BS EN 12831 heat loss calculation. Check radiator outputs against the manufacturer's data; heat pump installs need a proper room-by-room calculation.

Figures used

Room temperatures, air change rates and typical U-values behind the calculator.

Room design temperatures and air changes used
RoomDesign tempAir changes / h
Living room21 °C1.5
Bedroom18 °C1
Kitchen18 °C2
Bathroom22 °C3
Hall / landing18 °C2

Air change rates are the older CIBSE Domestic Heating Design Guide figures, suited to draughty, naturally ventilated homes. A modern, airtight house may be well under 1 air change per hour — edit the figure if you know better.

Typical U-values (W/m²K)
ElementU-value
Solid brick 220 mm, plastered2.10
Solid brick 105 mm (half brick)3.00
Cavity wall, unfilled1.47
Cavity wall, insulated0.50
Timber frame / modern insulated0.29
Single glazed (wood / PVCu)5.00
Single glazed, metal frame5.80
Double glazed (older)2.90
Low-E double glazed1.70
Triple glazed (about 1.0 or less)1.00
Floor: suspended timber, ventilated void0.82
Floor: solid floor on earth, uninsulated0.82
Ceiling: loft, 270 mm+ insulation0.16
Ceiling: loft, older / thin insulation0.71
Ceiling: loft, uninsulated2.30
Ceiling: flat roof, insulated0.70
Ceiling: flat roof, uninsulated2.19

Typical manufacturer heat-loss figures for UK construction. Real U-values vary with thickness, age and condition.

Radiator sizes for low-temperature systems

Radiators are rated at ΔT50 (BS EN 442 test). At a lower water temperature they give out less heat, so the catalogue figure has to be bigger.

Radiator correction factors (BS EN 442 test, ΔT50 = 1)
System ΔTFactorΔT50 rating for 1,000 Win BTU/h
ΔT601.268789 W2,691
ΔT551.132883 W3,014
ΔT501.0001,000 W3,412
ΔT450.8711,148 W3,917
ΔT400.7471,339 W4,568
ΔT350.6271,595 W5,442
ΔT300.5131,949 W6,651
ΔT250.4042,475 W8,446

Divide the heat the room needs by the factor to get the ΔT50 rating to look for in the catalogue. Example: a room needing 1,000 W on a heat pump running at ΔT30 needs a radiator rated about 1,950 W at ΔT50.

How the BTU figure is worked out

Heat leaves a room two ways: through the walls, windows, floor and ceiling (fabric loss), and with the air that leaks in and out (ventilation loss). The calculator adds both at the design conditions — the room at its comfort temperature and −3 °C outside.

Fabric loss

For each outside surface: U-value × area × (room temperature − outside temperature). The outside wall area is the wall length × room height, less the windows. Floors and ceilings next to another heated room are taken as no loss; unheated floors and lofts use the outside temperature, as in common manufacturer calculators.

Ventilation loss

0.33 × air changes per hour × room volume (m³) × temperature difference. 0.33 W is roughly the heat needed to warm one cubic metre of air by 1 °C in an hour.

Watts to BTU

1 W = 3.412 BTU/h, so 1 kW = 3,412 BTU/h. Radiator catalogues in the UK quote both.

ΔT50, ΔT40, ΔT30

ΔT is the mean water temperature minus the room temperature. A traditional boiler system at 75 °C flow and 65 °C return in a 20 °C room is ΔT50. Condensing boilers run more efficiently cooler, and heat pumps typically run ΔT30 or lower, so the radiators need to be larger — roughly double the ΔT50 size at ΔT30.

What this does not do

It ignores heat lost to unheated rooms next door, thermal bridges and the reduced loss to the ground for large floors, and it uses typical U-values. For a heat pump design, an MCS installation or a whole-house survey, use a full room-by-room heat loss calculation.

Questions heating engineers ask

How many BTU do I need for a room?

It depends on the size of the room, how many outside walls and windows it has, the insulation and the temperature you want. As an example, a 4 × 3.5 × 2.4 m living room at 21 °C with one unfilled cavity outside wall, 2 m² of older double glazing and heated rooms above and below needs about 810 W, roughly 2,750 BTU/h, on this method.

How do I convert watts to BTU?

Multiply watts by 3.412 to get BTU per hour. 1,000 W is about 3,412 BTU/h, and 2,000 BTU/h is about 586 W.

What size radiator do I need for a heat pump?

Work out the heat the room needs, then divide by the correction factor for the system ΔT: about 0.75 at ΔT40, 0.63 at ΔT35 and 0.51 at ΔT30. At ΔT30 the radiator's ΔT50 catalogue rating needs to be about twice the room's heat loss.

Is this a proper heat loss calculation?

No. It is a quick room estimate with typical U-values and air change rates. A heat pump design or an MCS installation needs a full room-by-room heat loss calculation to BS EN 12831 using the actual construction.

More free tools for plumbers & heating engineers

Boiler size calculator — combi, system or regular — kW guide› All free calculators for the trades›

Quotes, jobs and certificates from the van

Quote on site, dispatch callouts, keep CP12s and installation certificates against each job, and give the crew a 4-button app for timesheets.

See Graftum for plumbing & heating
© 2026 Graftum Ltd · Software for plumbing & heating firms · Free calculators · Privacy
An estimate, not a BS EN 12831 heat loss calculation; check radiator outputs with the manufacturer.
FOR FIRMS

Quoting the heating job?

Price boiler and radiator installs with labour and materials apart and send the quote as a link the customer opens on their phone.

Plumbing & heating softwareEstimatingStart free