Stair calculator (Approved Document K)

Floor-to-floor height in — risers, going, pitch and a pass or fail against the Building Regulations.

Work out the stair

Total rise is finished floor to finished floor. Enter the going you want; the calculator picks the fewest risers that pass, or set the number yourself.

—
Risers / treads—
Rise—
Going—
2R + G—
Pitch—
Total going (plan length)—
Pitch line, nosing to nosing—
Going range for this rise—
    RisersRise2R+GPitchOK?

    Pitch line length is the slope from the bottom nosing line to the top floor. Stringers need extra for the top and bottom cuts — set out full size before ordering timber.

    A guide to the Approved Document K limits (England). Building control has the final say — check the full document and any site-specific requirements.

    Stair rules — Approved Document K

    Approved Document K (2013 edition, England), Section 1.

    Approved Document K, Table 1.1 — rise and going (mm)
    StairRiseGoingMax pitch
    Private stair150–220220–30042°
    Utility stair150–190250–400—
    General access stair150–170250–400—

    For all three: 2R + G between 550 and 700 mm. Private = within one dwelling. Utility = escape, access for maintenance or any purpose other than the usual route between levels in buildings other than dwellings. General access = the usual route in other buildings and common areas of flats.

    Private stairs — fewest risers for common floor-to-floor heights
    Total riseRisersRiseGoing rangeMin total going
    2,40011218.2243–2632,430
    2,45012204.2227–2912,497
    2,50012208.3232–2832,552
    2,55012212.5237–2752,607
    2,60012216.7241–2662,651
    2,65013203.8227–2922,724
    2,70013207.7231–2842,772
    2,75013211.5235–2762,820
    2,80013215.4240–2692,880
    2,85013219.2244–2612,928
    2,90014207.1231–2853,003

    Going range meets the 220 mm minimum, 2R + G of 550–700 mm and the 42° maximum pitch. Total going = (risers − 1) × going.

    How to work out risers and going

    1. Measure the total rise from finished floor to finished floor — allow for floor finishes, screed and boards at both levels.
    2. Divide by the maximum rise (220 mm for a private stair) and round up to get the fewest risers. Every rise in a flight must be the same.
    3. Choose a going so that 2R + G is between 550 and 700 mm and, for a private stair, the pitch is no more than 42°.
    4. Treads = risers − 1 (the top “tread” is the landing). Total going = treads × going.

    Example: 2,640 mm total rise ÷ 220 = 12 risers of exactly 220 mm. With a 250 mm going: 2R + G = 690 mm ✓, pitch = tan⁻¹(220 ÷ 250) = 41.3° ✓. Eleven treads give a total going of 2,750 mm.

    Why 42° matters

    The maximum rise and minimum going (220 + 220) cannot be used together on a private stair: 220/220 is 45°. At a 220 mm rise the going has to be at least 245 mm to stay within 42°.

    Headroom

    Approved Document K asks for at least 2.0 m clear headroom over the whole stair, measured vertically from the pitch line, and over landings. In a loft conversion where there is not enough space, a reduced headroom is accepted: 1.9 m at the centre line of the stair, reducing to 1.8 m at the side.

    Other points to check

    Questions joiners ask

    What is the maximum rise for a stair in a house?

    Approved Document K allows a maximum rise of 220 mm and a minimum going of 220 mm for a private stair, with 2R + G between 550 and 700 mm and a maximum pitch of 42°. Because of the pitch limit, a 220 mm rise needs a going of at least about 245 mm.

    How many steps for a 2.6 m floor height?

    With a private stair, 2,600 mm ÷ 220 = 11.8, so 12 risers of about 217 mm. The going then needs to be roughly 241–266 mm to meet the 42° pitch and the 2R + G rule. There will be 11 treads.

    What is the 2R + G rule?

    Twice the rise plus the going should be between 550 and 700 mm. It keeps the step comfortable: for example a 200 mm rise with a 250 mm going gives 650 mm.

    What headroom does a loft conversion stair need?

    Normally 2.0 m above the pitch line. In a loft conversion where that cannot be achieved, Approved Document K accepts 1.9 m at the centre line of the stair reducing to 1.8 m at the side.

    More free calculators

    Flooring calculator — Laminate, LVT and engineered packs, underlay, skirting, screed› Plasterboard calculator — Boards, screws, tape and jointing for walls and ceilings› Brick calculator — Bricks, mortar, sand and cement for a wall› All free calculators for UK trades›

    Run your crew and jobs from the phone

    Clock-in, timesheets, quotes and CIS pay runs for joiners and small trade firms. First 3 months free.

    See Graftum